接地材料檢測公司提(ti)示您根據《電(dian)(dian)(dian)力工程接(jie)(jie)地(di)裝(zhuang)(zhuang)置選材(cai)導則》規(gui)定了(le)電(dian)(dian)(dian)力工程接(jie)(jie)地(di)裝(zhuang)(zhuang)置用材(cai)料或產品(pin)的(de)分(fen)類(lei)和(he)選擇(ze)要(yao)(yao)求(qiu),明確了(le)接(jie)(jie)地(di)材(cai)料選用時,需按照標準對(dui)接(jie)(jie)地(di)裝(zhuang)(zhuang)置區域土(tu)壤(rang)進(jin)行腐蝕性(xing)評價(jia),并對(dui)接(jie)(jie)地(di)裝(zhuang)(zhuang)置剩余壽命進(jin)行校核,同時要(yao)(yao)滿足環保要(yao)(yao)求(qiu),這主要(yao)(yao)適用于發電(dian)(dian)(dian)、輸變電(dian)(dian)(dian)、配電(dian)(dian)(dian)等電(dian)(dian)(dian)力工程接(jie)(jie)地(di)裝(zhuang)(zhuang)置的(de)材(cai)料或產品(pin)選擇(ze),不(bu)適用直(zhi)流接(jie)(jie)地(di)極材(cai)料選擇(ze)。
接地材料選用原則
1.土(tu)壤環境pH≤4.5時,不宜(yi)選用純(chun)銅和銅覆鋼;
2.pH<6和pH>12時,不宜選(xuan)用鋅包鋼;
3.濱海(hai)區(qu)域、填(tian)海(hai)區(qu)等高氯離子含(han)量(liang)區(qu)域不(bu)宜選用不(bu)銹鋼。
備注:上述幾(ji)點原則須(xu)開展(zhan)接地網土(tu)壤腐蝕(shi)性(xing)評(ping)(ping)價。土(tu)壤腐蝕(shi)性(xing)等級分(fen)為微、弱(ruo)、中和(he)強四個(ge)級別。腐蝕(shi)性(xing)評(ping)(ping)價宜優先選(xuan)用(yong)檢(jian)查片(pian)(pian)法(fa),當不(bu)具(ju)備埋片(pian)(pian)條件時,宜采用(yong)多指標評(ping)(ping)價,單指標評(ping)(ping)價作(zuo)為輔(fu)助。
(一(yi))接(jie)地主材的選用(yong)流程
1.通(tong)過埋片法(fa)、多指(zhi)標法(fa)和單(dan)指(zhi)標法(fa)等開展(zhan)土壤(rang)腐(fu)蝕性評價(jia);
2.對材料材質化(hua)學屬性、地下金屬構(gou)筑物信息(xi)及技術經(jing)濟(ji)性分析;
3.確定接地主材。
(二)接地輔材(cai)的選用流程
1.接地(di)主(zhu)材構成(cheng)的接地(di)網接地(di)電阻;
2.計算需降阻值;
3.選擇降阻方法;
4.通過土(tu)壤(rang)腐(fu)蝕性(xing)評價、接地主材(cai)材(cai)質(zhi)及主材(cai)地網(wang)布置和多(duo)間距土(tu)壤(rang)電阻率測量(liang)等來確定接地輔材(cai)的選擇,主要有(you)材(cai)質(zhi)、數量(liang)和布置方式。
根據不同的土(tu)壤情況及(ji)接(jie)地(di)電(dian)阻值的要(yao)求來確定(ding)不同的接(jie)地(di)材料,能夠(gou)在(zai)保證接(jie)地(di)效果的同時,延長接(jie)地(di)材料的使(shi)用(yong)壽命(ming),確保經濟合(he)理,才是(shi)合(he)格的防雷(lei)接(jie)地(di)工程。